Gas terugslagklep NV300, roestvrij staal (voorheen 338-ES)
Terugslagklep uit RVS ter voorkoming van ongewenste gasmengsels, voor flow tot 3.260 m³/h (Lucht), tot 16 bar Voor inzet in thermische processystemen EN746-2, G 1 - G 1.1/4
- Beveiligingselement: terugslagklep [NV]
- ieder appendage wordt 100% getest
- vlamterugslagzeker bij brandbare gassen-druklucht-mengsels
- biedt het geringste drukverlies – door een goed ventielsystem met de kleinste openingsdrukken (ca. 3,5 mbar)
- ideaal fvoor Biogasontzwavelings-systemen
- ideaalook bij het inbzettyn van corrosieve gassen
- Vuilfilter (100 μm)in de gasinlaat
- 65 X 115 mm, 1.500 g
Informatie
WITT non-return valves (check valves) for reliable protection against dangerous reverse gas flow. Every non-return valve (check valve) 100% tested.
Benefits:
- a spring-loaded non-return valve (check valve) prevents a return flow of gases which could lead to unwanted gas mixtures
- low pressure drops – using complex valve assembly with low opening pressures
- no leaks – using a spring-loaded valve assembly with elastomer sealing
- stainless steel filter (100 μm) in the gas inlet protects the non-return valve against dirt contamination, extending the service life
- diverse applications – useful for many technical gases
Operation / Usage:
- non-return valves (check valves) are used to protect equipment and pipelines against dangerous reverse gas flow. Use is possible for applications in accordance with EN 746-2
- ideal for use with corrosive gases in the chemical industry, process technology or in laboritories
- WITT non-return valves (check valves) may be mounted in any position / orientation the maximum ambient / working temperature is 70 °C / 158 °F
Maintenance:
- annual testing of the non-return valve (check valve) and body leak tightness is recommended
- WITT is happy to supply special test equipment
- non-return valves (check valves) are only to be serviced by the manufacturer. The dirt filter may be replaced by competent staff
Approvals
Company certified to ISO 9001and PED 2014/68/EC Module H
CE-marked in accordance with PED 2014/68/EC
Cleaned for Oxygen Service according to EIGA IGC Doc 13/12/E: Oxygen Pipeline and Piping Systems
Downloads