Non-Return Valve NV800
Non-return valve for the prevention of unintended gas mixtures, for flow rates up to 14000 m³/h (air), DN 80
- safety element: non-return valve [NV]
- every non-return valve 100% tested
- protects against flashbacks for fuel gas-compressed air-mixtures
- offer minimum pressure drops – using complex valve assembly with low opening pressures (approx. 6-8 mbar)
- dirt filter (100 μm) on gas inlet
- may be mounted in any position / orientation
- 200 X 350 mm, 20 kg
Information
WITT non-return valves for reliable protection against dangerous reverse gas flow.
Every non-return valve 100% tested.
Benefits:
- a spring-loaded non-return valve prevents a reverse flow of gases which could lead to unwanted gas mixtures
- low pressure drops – using complex valve assembly with low opening pressures, NV800 approx. 6 - 8 mbar
- no leaks – using of a spring-loaded valve assembly with elastomer sealing
- stainless steel filter (100 μm) in the gas inlet protects the non-return valve against dirt contamination, extending the service life
- diverse applications – useful for many technical gases
- reduce installation costs – the spring-loaded valve is not affected by gravity and may be installed in any orientation
Operation / Usage:
- non-return valves are used to protect equipment and pipelines against dangerous reverse gas flow. Use is possible for applications in accordance with EN 746-2
- non-return valves are proved in accordance with DIN EN ISO 5175-2. They may also be used as a safety device to protect against flashbacks (proved in accordance with DIN EN ISO 5175-1 point 6.7), which may result from the combustion of natural gas/ LPG with air
- the maximum ambient / working temperature is 70 °C / 158 °F
Maintenance:
- annual testing of the non-return valve and body leak tightness is recommended
- non-return valves are only to be serviced by the manufacturer
Approvals
Company certified to ISO 9001 and PED 2014/68/EU Module H
CE-marked in accordance with PED 2014/68/EU
Designed for Oxygen Service in accordance with EIGA 13/20 and CGA G-4.4: Oxygen Pipeline and Piping Systems
Cleaned for Oxygen Service in accordance with EIGA 33/18 and CGA G-4.1: Cleaning of Equipment for Oxygen Service
Downloads
Here you find all downloads for the product.