Beveiligings samenstel 645/85-30

Samenstel van 2 of 4 vlamdovers type 85-30 volgens de DIN EN ISO 5175-1 voor hoge flow

  • hoogste kwaliteit van de wereldmarktleider
  • beveiligingselementen: vlamdover [FA],  thermisch gestuurde afsluiter  [TV], gaskeerklep [NV]
  • ieder appendage wordt 100% getest
  • 285 X 430 mm, 44 kg (2-voudig), 53 kg (4-voudig)
  • Acetyleen max. 392 m³/h (vrije uitstroom)
  • Brandbare gassen max. 2.740 m³/h (vrije uitstroom)
  • Zuurstof max. 1.850 m³/h (vrije uitstroom)

Dit model is ook in RVS leverbaar

Datablad Downloads
Offerte aanvraag

Informatie

WITT Safety groups for reliable protection against dangerous reverse gas flow and flashbacks in accordance with DIN EN ISO 5175-1. For applications with high flow rates. Every safety group 100% tested.

Benefits:

  • a large surface area flame arrestor FA of stainless steel construction extinguishes any dangerous flashback
  • a temperature-sensitive cut-off valve TV extinguishes sustained flashbacks long before the internal temperature of the arrestors reaches a dangerous level
  • a spring-loaded non-return valve NV prevents slow or sudden reverse gas flow forming explosive mixtures in the gas supply

Operation / Usage:

  • in central gas supplies (behind the manifold pressure regulator or in a pipeline system)
  • in thermal processing systems conforming to EN 746-2 (cutting machines, furnace supply equipment)
  • WITT safety groups may be mounted in any position / orientation in pipelines / supply pipes
  • the maximum ambient / working temperature is 60 °C / 140 °F
  • gases: acetylene, natural gas, LPG, hydrogen, oxygen, ethylene, propane (more upon request)

Maintenance:

  • annual testing of the non-return valve, body leak tightness and flow capacity is recommended
  • safety groups are only to be serviced by the manufacturer

Options

  • connection: two-sided female thread (G-; NPT-; RC-thread)

Approvals
Company certified to ISO 9001 and PED 2014/68/EC Module H
CE-marked in accordance with PED 2014/68/EC
Cleaned for Oxygen Service according to EIGA IGC Doc 13/12/E: Oxygen Pipeline and Piping Systems