Gas terugslagklep 70 / 70U
Terugslagklep ter voorkoming van ongewenste gasmengsels, voor flow tot 1.120 m³/h (Lucht), tot 16 bar. Voor inzet in thermische processystemen EN746-2, G 3/4 - G 1.1/2
- Veiligheidselement: terugslagklep [NV]
- ieder appendage wordt 100% getest
- DIN EN ISO 5175-2
- vlamterugslagzeker bij brandbare gassen-perslucht-mengsels
- biedt weining drukverlies door een vernuftigd klepsysteem, openingsdruk (ca. 4 mbar)
- 62 X 137 X 160 mm, 1.255-1.679 g
Informatie
WITT non-return valves for reliable protection against dangerous reverse gas flow. Every non-return valve 100% tested.
Benefits:
- a spring-loaded non-return valve prevents a reverse flow of gases which could lead to unwanted gas mixtures
- low pressure drops – using complex valve assembly with low opening pressures (approx. 4 mbar)
- brass filter protects the non-return valve against flashbacks, extending the service life
- diverse applications – useful for many technical gases
- reduce installation costs – the spring-loaded valve is not affected by gravity and may be installed in any orientation
Operation / Usage:
- non-return valves are used to protect equipment and pipelines against dangerous reverse gas flow. Use is possible for applications in accordance with EN 746-2
- non-return valves are proved in accordance with DIN EN ISO 5175-2. They may also be used as a safety device to protect against flashbacks (proved in accordance with DIN EN ISO 5175-1 point 6.7), which may result from the combustion of natural gas/ LPG with air
- the maximum ambient / working temperature is 70 °C / 158 °F
Maintenance:
- annual testing of the non-return valve, body leak tightness and flow capacity is recommended
- WITT is happy to supply special test equipment
- non-return valves are only to be serviced by the manufacturer
Approvals
Company certified to ISO 9001 and PED 2014/68/EC Module H
CE-marked in accordance with PED 2014/68/EC
Designed for Oxygen Service in accordance with EIGA 13/20 and CGA G-4.4: Oxygen Pipeline and Piping Systems
Cleaned for Oxygen Service in accordance with EIGA 33/18 and CGA G-4.1: Cleaning of Equipment for Oxygen Service
Downloads
Hier vindt u de belangrijkste downloads van het product